FD 60 B-F / FD 60 B-C
Diesel generators
22.0 kVA - 66.0 kVA
Ask about this generator

Features of the unit
| Engine | Baudouin 4M10G70/5 |
| Exhaust emissions | fuel optimized |
| Fuel system | direct injection |
| Speed regulation | electronic |
| Frequency | 50Hz |
| ESP maximum power | 66.0 kVA / 53.0 kW |
| PRP rated power | 60.0 kVA / 48.0 kW |
| Fuel tank | 260 L |
| Alternator | Leroy Sommer TAL 042 H |
| Performance class | G3 (wg ISO 8528-5) |
Characteristics
- Digital voltage regulation +/-0.25%
- Three-phase voltage control
- Low disturbance level THD <2%
- Alternator short circuit capacity 270 % In (optional 300 %)
- Class H insulation
- Protection index IP23
- Performance class G3 (acc. ISO 8528-5)
- Ready to load just after start
- AMF and MRS functionality and protection
- Autonomy 21,0 h with 75 % load
- Compact design
- Forklift manouvable from the front and side wall
ComAp driver
InteliLite AMF 25

- Controller type: ComAp InteliLite AMF 25
- Support of Dual AMF/MRS applications
- Direct communication with EFI engines
- Total remote monitoring and control
- Intuitive operator interface, adjustable Main Screen
- Real time clock
- Comprehensive history log with up to 350 events
- 3 phase true RMS current and voltage measurement
- Both mains and generator voltage detection
- Active/Reactive Power and Power Factor per phase measurement
- Run Hours counter with source selector
- 3 maintenance timers (counting even under zero)
- Multipurpose flexible timers (also for rental)
- Battery voltage measurement
- Complete engine and alternator protection
- CAN modules support
- USB port on-board
- 2 slots for plug-in modules
- Plug-in module concept for more capabilities (RS232, RS485, Ethernet, GPRS, 4G/LTE, Modbus, SNMP, emails, SMS, I/Os)
- Cloud-based monitoring and control via WebSupervisor) (optional module required)
- Geofencing and tracking via WebSupervisor (optional module required)
- Control and monitoring over SMS (GSM module required)
- 3 levels of password protection
- In-built PLC, complemented with a monitoring/debugging tool, for additional functionality, if required
- Spare inputs and outputs available by default: binary input – 2, binary output – 1, analogue input – 3,
- A version for low temperature is also available
Baudouin engine
4M10G70/5
| Manufacturer | Baudouin |
| Type | 4M10G70/5 |
| Made in | China |
| Engine power | 57,0 kW |
| Emission standard | non-emission |
| Rotation per minute | 1500 rpm |
| Engine governor | electronic |
| Governor class | G3 (wg ISO 8528-5) |
| Displacement | 4,1 l |
| No of cylinder | 4 |
| Fuel system | direct injection |
| Electrical system | 12 V |
| Cooling system capacity | 18,0 l |
| Oil pan capacity | 14,0 l |
| Fuel type | Diesel (EN 590) |
Leroy Somer alternator
TAL 042 H
| Manufacturer | Leroy Somer |
| Type | TAL 042 H |
| Made in | The czech republic |
| Nominal voltage | 400 V |
| Nominal power factor (cos φ) | 0,8 |
| Ambient temperature, altitude | 40 ºC, 1000m n.p.m. |
| Nominal Power | 60.0 kVA |
| Protection index | IP 23 |
| No of bearing | single bearing |
| Coupling | direct |
| Technology | brushless |
| Short circuit maintaining capacity | 270% 10s |
| Efficiency | 89,9 % |
| Insulation class | H |
| Total harmonic content THD | <2 % |
| Reactance Xd'' | 7,3 % |
| Voltage regulator type | AVR, digital |
| Voltage measurement | 3 phases |
| Adjustment accuracy | +/- 0,25 % |
| AVR Power Supply | AREP+ |
| AVR supply optional | PMG |