FD 50 I-F / FD 50 I-C
Diesel generators
22.0 kVA - 66.0 kVA
Ask about this generator

Features of the unit
| Engine | FPT (Iveco) NEF45AM2 | 
| Exhaust emissions | fuel optimized | 
| Fuel system | direct injection | 
| Speed regulation | mechanical | 
| Frequency | 50Hz | 
| ESP maximum power | 55.0 kVA / 44.0 kW | 
| PRP rated power | 50.0 kVA / 40.0 kW | 
| Fuel tank | 260 L | 
| Alternator | Leroy Sommer TAL 042 G | 
| Performance class | G2 (wg ISO 8528-5) | 
Characteristics
- Digital voltage regulation +/-0.25%
- Three-phase voltage control
- Low disturbance level THD <2%
- Alternator short circuit capacity 270 % In (optional 300 %)
- Class H insulation
- Protection index IP23
- Performance class G2 (according to ISO 8528-5)
- Ready to load just after start
- AMF and MRS functionality and protection
- Autonomy 24,3 h with 75% load
- Compact design
- Forklift manouvable from the front and side wall
ComAp driver
InteliLite AMF 25

- Controller type: ComAp InteliLite AMF 25
- Support of Dual AMF/MRS applications
- Direct communication with EFI engines
- Total remote monitoring and control
- Intuitive operator interface, adjustable Main Screen
- Real time clock
- Comprehensive history log with up to 350 events
- 3 phase true RMS current and voltage measurement
- Both mains and generator voltage detection
- Active/Reactive Power and Power Factor per phase measurement
- Run Hours counter with source selector
- 3 maintenance timers (counting even under zero)
- Multipurpose flexible timers (also for rental)
-  Battery voltage measurement
-  Complete engine and alternator protection
-  CAN modules support
-  USB port on-board
-  2 slots for plug-in modules
-  Plug-in module concept for more capabilities (RS232, RS485, Ethernet, GPRS, 4G/LTE, Modbus, SNMP, emails, SMS, I/Os)
-  Cloud-based monitoring and control via WebSupervisor) (optional module required)
-  Geofencing and tracking via WebSupervisor (optional module required)
-  Control and monitoring over SMS (GSM module required)
-  3 levels of password protection
-  In-built PLC, complemented with a monitoring/debugging tool, for additional functionality, if required
-  Spare inputs and outputs available by default: binary input – 2, binary output – 1, analogue input – 3,
-  A version for low temperature is also available
FPT engine (Iveco)
NEF45AM2
| Manufacturer | FPT (Iveco) | 
| Type | NEF45AM2 | 
| Made in | Italy | 
| Engine power | 45,0 kW | 
| Emission standard | non-emission | 
| Rotation per minute | 1500 rpm | 
| Engine governor | mechanical | 
| Governor class | G2 (wg ISO 8528-5) | 
| Displacement | 4,5 l | 
| No of cylinder | 4 | 
| Fuel system | direct injection | 
| Electrical system | 12 V | 
| Cooling system capacity | 17,0 l | 
| Oil pan capacity | 12,8 l | 
| Fuel type | Diesel (EN 590) | 
Leroy Somer alternator
TAL 042 G
| Manufacturer | Leroy Somer | 
| Type | TAL 042 G | 
| Made in | Czech Republic | 
| Nominal voltage | 400 V | 
| Nominal power factor (cos φ) | 0,8 | 
| Ambient temperature, altitude | 40 ºC, 1000m n.p.m. | 
| Nominal Power | 50.0 kVA | 
| Protection index | IP 23 | 
| No of bearing | single bearing | 
| Coupling | direct | 
| Technology | brushless | 
| Short circuit maintaining capacity | 270% 10s | 
| Efficiency | 89,4 % | 
| Insulation class | H | 
| Total harmonic content THD | <2 % | 
| Reactance Xd'' | 7 % | 
| Voltage regulator type | AVR, digital | 
| Voltage measurement | 3 phases | 
| Voltage accuracy | +/- 0,25 % | 
| AVR Power Supply | AREP | 
| AVR supply optional | PMG | 


 
 