FD 160 C-F / FD 160 C-Q
Diesel generators 85.0 kVA - 271.0 kVA
Ask about this generator

Features of the unit
| Engine | Cummins 6BTAA5.9-G7 |
| Emission standard | fuel optimized |
| Fuel system | mechanical pump |
| Speed control | ECU |
| Frequency | 50Hz |
| ESP maximum power | 171.0 kVA / 137.0 kW |
| PRP rated power | 156.0 kVA / 125.0 kW |
| Fuel tank | 900 L |
| Alternator | Linz PRO22M G/4 |
| Performance class | G3 (wg ISO 8528-5) |
Characteristics
- Digital voltage regulation +/- 0,25 %
- One phase voltage control
- Low disturbance level THD <3%
- Class H insulation
- Alternator short circuit capacity 300% 10s ln
- Performance class G2 (according to ISO 8528-5)
- Ready to load just after start
- AMF and MRS functionality and protection
- Autonomy 27,9 h with 75 % load
- Protection index IP23
Unit Specification Sheets
Selected advantages
of Q-Series Canopies
Lista usług
-
Large Fuel TanksElement listy 1
Equipped with spacious fuel tanks, ensuring extended operation without frequent refueling.
-
Two Fuel InletsElement listy 2
One of the inlets can be extended outside, providing added convenience for refueling.
-
Retention TrayElement listy 3
An integrated retention tray prevents fuel or oil leaks, ensuring environmental protection.
-
Easy Service AccessElement listy 4
Ergonomic design allows for easy access from all sides, simplifying maintenance and inspections.
-
Additional Sockets and Protections
In power ranges from 20 to 250 kVA, the canopies allow for the installation of additional sockets and protections.
-
Optional Dust Filters
The air intake can be optionally protected with dust filters, enhancing durability and performance.
-
Anchoring Points
Four anchoring points ensure stability by securing the unit to the ground during operation.
-
UV Protection for Controller
Integrated retention tray prevents leaks, ensuring compliance with environmental regulations.
-
Corrosion-Resistant Screw Covers
Screws are protected with anti-corrosion covers, increasing the durability of the canopy.

ComAp driver
InteliLite AMF 25

| Controller type: ComAp InteliLite AMF 25 |
| Support of Dual AMF/MRS applications |
| Direct communication with EFI engines |
| Total remote monitoring and control |
| Intuitive operator interface, adjustable Main Screen |
| Real time clock |
| Comprehensive history log with up to 350 events |
| 3 phase true RMS current and voltage measurement |
| Both mains and generator voltage detection |
| Active/Reactive Power and Power Factor per phase measurement |
| Run Hours counter with source selector |
| 3 maintenance timers (counting even under zero) |
| Multipurpose flexible timers (also for rental) |
| Battery voltage measurement |
| Complete engine and alternator protection |
| CAN modules support |
| USB port on-board |
| 2 slots for plug-in modules |
| Plug-in module concept for more capabilities (RS232, RS485, Ethernet, GPRS, 4G/LTE, Modbus, SNMP, emails, SMS, I/Os) |
| Cloud-based monitoring and control via WebSupervisor) (optional module required) |
| Geofencing and tracking via WebSupervisor (optional module required) |
| Control and monitoring over SMS (GSM module required) |
| 3 levels of password protection |
| In-built PLC, complemented with a monitoring/debugging tool, for additional functionality, if required |
| Spare inputs and outputs available by default: binary input – 2, binary output – 1, analogue input – 3 |
| A version for low temperature is also available |
Cummins engine
6BTAA5.9-G7
| Engine manufacturer | Cummins |
| Engine model | 6BTAA5.9-G7 |
| Country of production | Belgium |
| Net engine power | 134,0 kW |
| Exhaust gas emissions | fuel optimized |
| Turnover | 1500 rpm |
| Speed control | ECU |
| Build class | G2 (wg ISO 8528-5) |
| Engine capacity | 5,9 l |
| Number of cylinders | 6 |
| Fuel system | mechanical pump |
| Installation | 12V |
| Coolant capacity | 22,1 l |
| Oil pan capacity | 16,4 l |
| Fuel type | Diesel (EN 590) |
Linz alternator
PRO22M G/4
| Generator manufacturer | Linz |
| Generator model | PRO22M G/4 |
| Country of production | Italy |
| Nominal voltage | 400V |
| Power factor (cos φ) | 0,8 |
| Temperature, altitude | 40 ºC, 1000m n.p.m. |
| Rated power | 160.0 kVA |
| Degree of protection | IP 23 |
| Design | single bearing |
| Connection with the engine | direct |
| Technology | brushless |
| Short circuit current maintenance | 300% 10s |
| Efficiency | 93,1 % |
| Insulation class | H |
| Harmonic Content THD | <3% |
| Reactance Xd'' | 8 % |
| Voltage regulation | AVR HVR-11 |
| Voltage measurement | 3 phases |
| Adjustment accuracy | +/- 0,25 % |
| AVR Power Supply | auxiliary winding |